Cool every AI rack in Hall C. Keep the hall you have.

Liquid straight to the chip, 120 kW per rack, on the warm facility water you already run. Built one row at a time.

Prepared forCorvia Cloud
SiteRidgeview campus, Hall C, AI row 1
InsideDesign, diagrams, documents, pilot and delivery
StatusFor your design review
38 °C IN 48 °C OUT
In this kit

Everything your team needs, in one place.

Each part is written for the person who has to sign off on it. Jump to yours.

01 Why this design

Air stops at about 40 kW a rack. Your new servers start at 120.

Hall C was built for air. The racks going into AI row 1 put out three times the heat air can move. This design takes that heat off the chips with liquid and hands it to the facility water loop you already have.

120 kW
per rack, with room left on the CDU for three more racks.
32 °C
facility water is all it needs. Dry coolers do most of the work.
N+1
pumps in every CDU. A failed pump swaps out with the row running.
1 rack
is the most a leak can take offline. The rest of the row keeps flowing.

Liquid where the heat is

Cold plates sit on the CPUs and GPUs. About 85% of the heat leaves in the coolant. A rear door catches the rest before it reaches the room.

Two loops that never mix

Your facility water stays on one side of the CDU. Clean, filtered coolant runs to the servers on the other. A plate heat exchanger moves heat between them.

Built to be serviced live

Dry-break couplings at every tray. Valves at every rack. Filters and pumps change from the front without stopping the row.

Built for everyone who signs off

Mechanical and facilities

Warm water, sized flows, one tap per row. Sections 06 and 07.

Critical power

15 kW per CDU at most, dual feeds, N+1 pumps. Section 08.

IT and hardware ops

Pull a server without draining. Map to your cold plates. Section 09.

Data center ops

Every point in your BMS. One leak, one rack. Section 12.

Procurement

Per-rack kits, five-year warranty, one vendor to call. Section 11.

02 About Arvane

We cool racks that run hot.

Liquid to the chip, heat out of the building, and nothing on the floor.

Arvane Thermal designs the Tidepath line of coolant distribution units, rack manifolds, rear doors and leak protection. We build it for halls that were designed for air and now have to carry AI loads.

We do not hand you a parts list. We draw your rows, size every pipe, pressure-test every manifold and hose before it ships, label it to the drawing, and stand next to your team when the loop fills for the first time.

2016Founded in Port Calder, CA
One roofDesign, build, pressure test, support
5 yearsHardware warranty, advance replacement
One engineerNamed to your site, start to finish

How we run your project

1

Design

We draw your rows and racks, size every flow, and agree them with your engineers.

2

Prove

A pilot rack runs at full load on a load bank. You test it against a pass list you approve.

3

Kit

We build, pressure-test, cap and label each rack kit. One crate per rack.

4

Commission

We fill, flush and load-test with your team, then stay on the account. Same person, same number.

03 System at a glance

Eight parts. One CDU per row.

The CDU feeds every rack in the row through overhead headers. The colors here are used in every diagram in this kit.

RoleProductPart numberKey pointPower
Cooling, rowIn-row coolant distribution unitTP-C12001.2 MW. N+1 pumps. Facility water and server coolant never mix.2x 400-480 VAC, 3-phase
Cooling, rackIn-rack CDU, 4UTP-C120120 kW. For a pilot rack or a single high-density rack.2x 208-415 VAC
DistributionRear rack manifold, 0UTP-M4824 supply and 24 return ports. Flow and temp sensing built in.None
DistributionDry-break quick disconnectTP-Q12Push to connect. No drip on release. One pair per tray.None
DistributionIsolation valve setTP-VMotorized. Shuts one rack off the header in seconds.24 VDC from TP-LX
Air sideRear-door heat exchangerTP-RD5050 kW. Catches the heat the cold plates miss.208-240 VAC, fans
SafetyLeak controller and ropeTP-LX / TP-LRFinds a leak to within 1 m and closes that rack's valves.100-240 VAC
MonitoringMonitoring softwareTP-ViewEvery flow, pressure, temp and leak point. Talks to your BMS.Your VM or ours
Your equipmentArvane productCoolant distribution unitIT rack or serversFacility or third partyOption or room to growCoolant supplyCoolant returnFacility waterPower or airLeak sensingMonitoring and control
04 Product guide

Cooling, sized to the row or the rack.

Pick the CDU by how many racks it feeds. Add a rear door wherever air heat is left over.

ARVANE
TP-C1200

In-row CDU

Sits at the end of the row like a rack. Moves heat from your server coolant into facility water.

Capacity
1,200 kW at 6 K approach
Coolant flow
Up to 1,800 L/min
Supply temp
25 to 45 °C, held to ±0.5 K
Pumps
N+1, variable speed, hot-swap
Filtration
50 µm, change without shutdown
Power
2x 400-480 VAC, up to 15 kW
Size
800 x 1200 x 2200 mm
Full datasheet in section 08.
TP-C120

In-rack CDU

One rack on its own: a pilot, a lab, or a single dense rack in an air-cooled hall.

Capacity
120 kW at 6 K approach
Coolant flow
Up to 180 L/min
Pumps
Redundant pair, hot-swap
Filtration
50 µm
Power
2x 208-415 VAC
Size
4U, 1000 mm deep
TP-RD50

Rear-door heat exchanger

Hangs on the back of the rack. Takes the 15% of heat that still goes to air.

Capacity
Up to 50 kW
Fans
EC, speed set by exhaust temp
Water
From the CDU loop or facility water
Fit
42U and 48U, 600 or 800 mm racks
Power
208-240 VAC, under 900 W
Hinge
Left or right, swings 180°

Distribution and protection

TP-M48

Rear rack manifold

Mounts in the rear 0U space. Feeds every tray in the rack from one supply and one return.

Ports
24 supply, 24 return
Couplings
TP-Q12 dry-break on every port
Inlet
1.5" with TP-V isolation valves
Sensing
Flow, inlet and outlet temp
Material
316 stainless steel
Rated
10 bar working pressure
Setup guide in section 09.
SUPPLY · RETURN
TP-Q12

Dry-break quick disconnect

The coupling at every tray. Pull a server without draining anything.

Size
1/2" flow path
Flow
Up to 30 L/min
Spill
Under 0.05 mL per disconnect
Colors
Blue supply, red return, keyed so they cannot swap
Seals
EPDM, glycol-rated
Rated
10 bar working pressure
R4 · 2.1m
TP-LX + TP-LR

Leak controller and sensing rope

Rope runs under every rack and CDU. The controller finds the leak and acts on it.

Zones
Up to 4 ropes, 150 m each
Locate
To within 1 m
Action
Closes that rack's TP-V valves
Alerts
Relay out, BACnet, Modbus, SNMP
Power
100-240 VAC
Rope
3, 6 and 15 m lengths
One leak closes one rack. The rest of the row keeps running.

Monitoring and service

TP-View

Monitoring software

Every CDU, manifold, door and leak point on one screen, with the same names in your BMS.

Points
Flow, pressure, temps, pump state, leaks
Out
BACnet/IP, Modbus TCP, SNMPv3, REST API
Alerts
Email and webhook, by severity
Runs on
Your VM, on your management network
Cloud
Not required
TP-FILL

Fill and service cart

Fills, bleeds and tops up a loop. Comes with the pilot and every row kit.

Tank
200 L
Filter
25 µm on fill
Pump
Variable speed, pressure-limited
Power
120-240 VAC
PG25PG25
PG25

Coolant

Propylene glycol, 25%, with corrosion inhibitor. Pre-mixed, so nothing is mixed on site.

Ships
200 L drums or 1,000 L totes
Checks
Quarterly sample, we test it
Option
Treated water, if your team prefers
Scroll sideways to see the full diagram →
SUPPLY ROW, 24 PORTS (TOP) · RETURN ROW, 24 PORTS (BOTTOM)18 pairs used, one per compute tray6 pairs free for added trays or a switch trayEvery port: dry-break TP-Q12
TP-M48 port plan. A rack of 18 liquid-cooled trays uses 18 of 24 port pairs. The six spare pairs take added trays or a liquid-cooled switch later, with no new manifold.
05 Reference designs

Prove one rack. Run a row. Grow to the hall.

Three designs, each a step up from the last. All three use the same parts, so nothing you buy for the pilot is wasted.

Your equipmentArvane productCoolant distribution unitIT rack or serversFacility or third partyOption or room to growCoolant supplyCoolant returnFacility waterPower or airLeak sensingMonitoring and control
Design 1

Pilot rack

One rack with its own in-rack CDU. Proves the cooling, the leak response and the BMS link before the row goes in.

Scroll sideways to see the full diagram →
YOUR FACILITYCOOLINGDISTRIBUTIONYOUR ITFacility waterYour loop, 32 °C supplyTP-C120In-rack CDU120 kW, liquid to liquidPWR A/B feeds32 °C44 °CTP-M48 rack manifold18 of 24 port pairs used38 °C48 °C18 compute traysCold plates on CPUs and GPUsTP-Q12TP-RD50 rear doorTakes the leftover air heatRack exhaust airLeaves near room temperatureAirTP-LR leak rope under the rack and the CDUTP-LX leak controllerCloses the rack valvesTP-View monitoringCDU, manifold, leak dataCorvia BMS and DCIMYour systemsBACnetOne rack, full load, before a single GPU arrives. This is the evaluation kit in section 10.
Design 1. Facility water in, server coolant out, a rear door for the air heat, and a leak rope that can shut the rack off on its own.
Design 2

One AI row: the Hall C proposal

One in-row CDU feeds eight 120 kW racks through overhead headers. Every rack has its own valves, rear door and leak coverage.

Scroll sideways to see the full diagram →
Dry coolers, chillersYour plant, 32 °CFacility water 32 °C44 °C backBusway A and BTwo independent feedsTP-C1200In-row CDU1.2 MWN+1 pumpsPWR A/B 400 VSupply header38 °CReturn header48 °CRack 1120 kWRD50 doorRack 2120 kWRD50 doorRack 3120 kWRD50 doorRack 4120 kWRD50 doorRack 5120 kWRD50 doorRack 6120 kWRD50 doorRack 7120 kWRD50 doorRack 8120 kWRD50 doorTP-LR leak rope under every rack and the CDUTP-LX leak controllerCloses one rack's valvesTP-View monitoringEvery sensor, one screenCorvia BMS and DCIMBACnet, Modbus or SNMPCDU flow, pressure, tempsTP-V isolation valves at every drop: one rack can be shut off while the row keeps running8 racks x about 102 kW to liquid = 816 kW on a 1.2 MW CDU. Room for three more racks on the same unit.
Design 2. 816 kW to liquid on a 1.2 MW CDU, with valves at every drop so one rack can be isolated while the row runs.
Design 3, option

The whole hall

Each row gets two CDUs for N+1. A facility water ring main joins them all to your plant.

Scroll sideways to see the full diagram →
Row ATODAYTP-C1200DutyTP-C1200Standby8-10racks120 kWRow BOPTIONTP-C1200DutyTP-C1200Standby8-10racks120 kWRow COPTIONTP-C1200DutyTP-C1200Standby8-10racks120 kWFacility water ring mainYour plantDry coolers, chillers, pumpsCentral TP-ViewEvery row, one screenCorvia BMS and DCIMSame points, same namesHeat reuseWarm return water, put to work
Design 3. Row A today. Rows B and C use the same kits on the same ring main, with one TP-View and the option to put the warm return water to work.
06 Row and rack

Where it all goes.

A sample layout for AI row 1 and one of its racks. Final positions are yours; we redraw this after the site walk.

Scroll sideways to see the full diagram →
AI ROW, TOP VIEWCold aisleCDUR1R2R3R4R5R6R7R8Contained hot aisle. Headers run overhead here, never over the cold aisle.FWLXLeak controllerRear doors (blue edge) take the air heat the cold plates miss.EntryTHE HEAT PATHChip cold platesCPUs and GPUsCoolant out, 48 °CTP-M48 rack manifoldDry-break at every trayBack to the CDUTP-C1200 heat exchangerFluids never mixHeat crosses overFacility water loop32 °C in, 44 °C outOut of the buildingDry coolers on the roofYour plant
Row layout and heat path. The CDU sits at the end of the row. Headers run overhead in the contained hot aisle. Heat goes from chip to coolant, coolant to facility water, and facility water to the roof.

Why the hot aisle

Pipes stay out of the cold aisle, where people work and servers breathe. Any drip lands where the rope is.

Why a CDU per row

One row on one unit keeps fault domains small. Add a row, add a CDU. Nothing upstream changes.

Why rear doors too

Cold plates miss memory, drives and power supplies. The door takes that heat, so your existing CRAHs are not asked to do more.

Scroll sideways to see the full diagram →
ONE RACK, SIDE BY SIDETop-of-rack switches (air)Compute trays 1-9Liquid-cooledPower shelvesCompute trays 10-18Liquid-cooledPower shelfLeak rope trayTP-V valvesTP-M48 manifoldrear 0U, blue in, red outTP-RD50 rear doorcatches the air heatFrontRearWHERE ONE RACK’S HEAT GOES (EXAMPLE)102 kW to liquid, 85%18 kWCold plates carry most of it. The rear door takes the rest, so theroom air stays where your CRAHs already hold it.WHAT ONE ROW ADDS UP TO8 racks x 102 kW to liquid816 kWTP-C1200 capacity1,200 kWHeadroom on the same CDU384 kWAir to rear doors, 8 x 18 kW144 kWTP-RD50 capacity, 8 x 50 kW400 kWExample load. We redo this from your server specs before the quote.
One rack, side by side. Trays at the front, manifold and rear door at the back, valves on top, leak rope at the base. Right: an example heat split, redone from your server specs before the quote.
07 Piping and fluids

Two loops. Each has its own rules.

Your facility water and our server coolant meet only inside the CDU. Here is who owns what, and how each part is built.

Yours

Facility water system (FW)

Runs
Your plant to each CDU
Temps
32 °C supply, about 44 °C back
Flow
About 1,500 L/min per CDU at full load
Fluid
Your water treatment, untouched
Tap
DN100 grooved at the CDU
Ours

Technology cooling system (TCS)

Runs
CDU to every cold plate and back
Temps
38 °C supply, 48 °C return
Flow
About 1.5 L/min per kW
Fluid
PG25, filtered to 50 µm
Build
316 stainless headers, EPDM hoses

Rules for every loop

  • Facility water and server coolant never share a pipe. The CDU's plate heat exchanger is the only place they meet.
  • Blue is always supply, red is always return. Couplings are keyed so they cannot be swapped.
  • Every header, drop and hose is pressure-tested before it ships, then flushed, dried and capped.
  • Fill and flush on site with the TP-FILL cart. Nothing is mixed on the floor.

Every pipe, hose and connection, by name

PartWhere it goesGuidance
Facility water (FW) mainsYour plant to the CDUYour pipe and your spec. DN100 grooved at the CDU. We give you flow and temps.
TCS headersCDU to the row, overhead in the hot aisle316 stainless, DN80. Pressure-tested before it ships. Supply blue, return red.
Rack dropsHeader to the TP-V valves on each rack1.5" braided hose, cut to your drawings. Pressure-tested and capped.
Tray hosesManifold port to serverEPDM, 1/2", TP-Q12 on both ends. Length per tray position.
Isolation valvesTop of every rack dropTP-V motorized pair. Manual override on the handle.
Bleed and drainTop and bottom of every manifoldBleed at the top, drain at the bottom, both capped in normal use.
Leak ropeUnder every rack and the CDUTP-LR, on clips, never under a pipe joint you cannot reach.
CDU powerBusway A and B to the CDU2x 400-480 VAC, 3-phase. Internal transfer between feeds.
Monitoring networkCDU, TP-LX and doors to TP-ViewYour management VLAN. RJ45, or RS-485 for Modbus RTU.
08 Datasheet

TP-C1200 in-row CDU.

The full two-page sheet your engineers will ask for. Every Tidepath datasheet follows the same order, so nothing takes hunting for.

arvaneTHERMAL
TP-C1200

In-Row Coolant Distribution Unit

Tidepath direct-to-chip liquid cooling

ARVANE
1.2 MWCooling capacity at 6 K approach
N+1 pumpsHot-swap from the front
±0.5 KSupply temperature control
50 µmFiltration, changed while running
Facility water, 32 °C→TP-C1200→TCS headers, 38 °C→TP-M48→Cold plates
Overview

The TP-C1200 cools a full row of high-density racks. It takes facility water on one side and server coolant on the other, and a plate heat exchanger moves the heat between them without the two ever mixing. Pumps run N+1 and swap out from the front. Every reading goes to TP-View and your BMS.

Applications
  • AI training and inference rows at 60 to 150 kW per rack
  • Retrofits of air-cooled halls with warm facility water
  • New builds that want dry coolers instead of chillers
Features
  • 1,200 kW at 6 K approach temperature
  • N+1 variable-speed pumps, hot-swap
  • Supply temp held to ±0.5 K
  • Duplex 50 µm filters, change without shutdown
  • Dual A/B power with internal transfer
  • Flow, pressure and temp at every port
  • BACnet/IP, Modbus TCP, SNMPv3, REST API
  • Front service only. Fits a standard row
Arvane Thermal · Port Calder, CA (fictional) · arvane.exampleDS-TPC1200 · Rev C · Nov 2026 · Page 1 of 2
Thermal
Capacity1,200 kW at 6 K approach
TCS supply temp25 to 45 °C, ±0.5 K
TCS flowUp to 1,800 L/min
Design ΔT10 K across the rack
FW supply tempUp to 35 °C
Hydraulics
Pumps3 (N+1), variable speed
Available head2.5 bar at full flow
FiltrationDuplex, 50 µm
CoolantPG25, or treated water
ConnectionsFW DN100 grooved; TCS DN100 flanged
Working pressure10 bar max
Electrical
Input2x 400-480 VAC, 3-phase, 50/60 Hz
DrawUp to 15 kW
TransferInternal, A to B
Controls
Local10" touchscreen
NetworkBACnet/IP, Modbus TCP, SNMPv3, REST
SerialModbus RTU, RS-485
Physical and environmental
Size800 W x 1200 D x 2200 H mm
Weight1,150 kg dry, 1,320 kg filled
Ambient10 to 40 °C, 5 to 90% RH
ServiceFront only
Drawing
ARVANEFRONT10" touchscreen, local controlFront-service pump and filter baysDrain and fill ports, lower frontPower A / BTop entryNetwork, BMS2x RJ45, RS-485FW: DN100 grooved · TCS: DN100 flangedTOP CONNECTIONS800 W x 1200 D x 2200 H mm
Compliance
CEUKCARoHSREACH
Ordering information
TP-C1200-SIn-row CDU, standard pumps
TP-C1200-HIn-row CDU, high-head pumps
TP-PMP-1200Spare pump module
TP-FLT-50Filter element, 50 µm
TP-VIEW-CTP-View license, per CDU
Fictional product. Every specification is mock data. Specifications subject to change without notice.DS-TPC1200 · Rev C · Page 2 of 2
09 Setup guide

TP-M48 rack manifold, mount to full flow.

Seven steps for your installer. One action per line, lettered callouts that match the drawing, and the pressure warning where it belongs.

arvaneTHERMAL
TP-M48 · TP-V · TP-Q12

Rack Manifold Setup Guide

Mount, fill, test, flow

This guide is for an experienced mechanical installer. It covers mounting the TP-M48 rear rack manifold, connecting it to the row header through TP-V valves, filling, pressure testing and first flow to the trays.

IMPORTANT Read the full specifications at arvane.example first. Work only on a rack that is isolated from the header. Coolant is under pressure in normal use.
ABCDEFGTP-M48, REAR VIEWTP-Q12 COUPLINGPush to connect, sleeve back to release
Manifold

ASupply ports, blue, 24
BReturn ports, red, 24
CTP-V isolation valves, top inlet
DBleed valve, top of return
EDrain valve, bottom

Sensing and mounting

FFlow and temperature sensor
G0U mounting brackets

Installation
Step 1. Prepare the rack
  1. Check the rear 0U channel is clear, top to bottom.
  2. Fit the brackets G at the marked heights.
  3. Torque bracket screws to 6 Nm.
TIP Leave the factory caps on every port until Step 7.
Step 2. Isolate the rack

Confirm both TP-V valves C are closed and locked out in TP-View before you touch the drop.

Step 3. Mount the manifold
  1. Lift the manifold onto the brackets. Two people.
  2. Blue column on the left, red on the right.
  3. Fit the retaining pins.
Step 4. Connect the drops
  1. Connect the blue drop to the supply inlet, red to return.
  2. Hand-tight, then a quarter turn.
  3. Check the labels match the rack number.
CAUTIONCoolant is under pressure in service. Wear eye protection and gloves. Never loosen a fitting on a rack that is not isolated. TP-Q12 couplings are the only parts made to break under pressure.
Arvane Thermal · Port Calder, CA (fictional) · arvane.exampleQS-TPM48 · Rev A · Page 1 of 2
Step 5. Fill and bleed
  1. Open supply valve C a quarter turn.
  2. Open bleed D until coolant runs clear, no air.
  3. Close the bleed. Open both valves fully.
Step 6. Pressure test
  1. Hold at 15 bar, 1.5x working pressure, for 30 minutes.
  2. Pass: no drop on the TP-View trend.
  3. Check the leak rope reads dry.
Step 7. Connect the trays
  1. Remove port caps one pair at a time.
  2. Push each TP-Q12 home until it clicks.
  3. Confirm flow on that port in TP-View.
Normal readings
PointNormal at full load
FInlet temp38 °C, ±0.5 K
FRack ΔT8 to 10 K
Flow per tray8 to 10 L/min
Leak statusDry, green in TP-View

Anything outside these ranges raises a warning in TP-View and in your BMS.

Application diagram
TP-C1200 Header TP-V valves 1.5" braided drop TP-M48 TP-Q12 Compute trays

Figure 1. Supply path into one rack. Return follows the same path back on the red side.

Fictional product. Every specification is mock data. Specifications subject to change without notice.QS-TPM48 · Rev A · Page 2 of 2
10 Pilot rack

Run it at full load before a single GPU arrives.

Design 1, shipped with a 120 kW liquid load bank in place of servers. Your team proves the cooling, the leak response and the BMS link on your floor.

ItemPart numberQty
In-rack CDUTP-C1201
Rear rack manifoldTP-M481
Isolation valve setTP-V1
Dry-break couplings, pairsTP-Q1224
Rear-door heat exchangerTP-RD501
Leak controller and ropesTP-LX / TP-LR1 / 2
Liquid load bank, 120 kWTP-LB1201
Monitoring software, pilot licenseTP-View1
Coolant, PG25 pre-mixedPG25200 L
Fill and service cartTP-FILL1
Hose kit, pre-cut and pressure-testedKIT-HOSE-PILOT1 set

How it ships

  • Manifold, valves and hoses pressure-tested, flushed and capped.
  • CDU set to your temps and on your management network.
  • Every part labeled to match the drawing.
  • Test reports with serial numbers in the crate.
  • An Arvane engineer on site to fill and start it with your team.

To decide with you

  • Pilot length and return terms. We suggest six weeks.
  • Which rack position, and where it taps facility water.
  • Who from your team runs the tests.
  • When real servers replace the load bank, if you want to keep it.

What a pass looks like

We draft this list. You edit it. The pilot passes when your team checks every line.

  • Holds 38 °C supply at 120 kW for 72 hours straight.
  • Rack ΔT stays between 8 and 10 K.
  • Pull one pump: the other carries full load, no alarm past a warning.
  • Disconnect a TP-Q12 under flow: nothing on the absorbent pad.
  • Wet the leak rope: alert in seconds, that rack's valves close.
  • Every point shows up in your BMS with the agreed names.
  • Facility water stays inside the agreed temps and flow.
  • Change a filter with the loop running.
11 Kitting and delivery

One crate per rack, ready to mount.

We build, pressure-test and label each rack kit, then ship it to your integrator ready to install.

1. OrderOne kit number per rack
2. BuildManifolds, valves, hoses cut to your drawings
3. TestEvery assembly at 1.5x working pressure
4. Flush and capClean, dry, sealed
5. Label and packBy row, rack and port
6. ShipTo your integrator, with serials and test reports

Kit numbers

  • KIT-RACK-DLC Manifold, valves, hoses, couplings, sensors
  • KIT-RDHX Rear door with hoses
  • KIT-ROW-8 CDU, headers and eight rack kits
  • KIT-LEAK Controller and ropes per row
  • KIT-FILL Coolant and fill cart

In every crate

  • Parts built for that rack position.
  • Every part labeled by row, rack and port.
  • Packing list and the rack drawing.
  • This setup guide, printed.
  • Pressure test report with serial numbers.

What your integrator gets

  • Fewer SKUs to stock: one kit per rack type.
  • A serial list ready for your DCIM asset records.
  • No cutting or fitting on the floor.
  • An optional spares kit per row: pump, filters, couplings.
12 Questions buyers ask

Straight answers, by team.

The questions we hear in every design review. If yours is not here, it goes on the list for the site walk.

Mechanical and facilities

Do we need chilled water?

No. The CDU runs on 32 °C facility water. That is warm enough for dry coolers to carry it most of the year, so your chillers only trim.

What does the CDU need from our plant?

Facility water at up to 35 °C, about 1,500 L/min per CDU at full load, and a DN100 tap. We give you the flow and pressure drop in writing.

What if facility water stops?

The CDU alarms at once and TP-View tells your BMS. Servers throttle on their own limits. We size ride-through time with you during design.

Critical power

How much power does the CDU draw?

Up to 15 kW at full flow, usually far less. Two feeds, A and B, with transfer inside the unit.

What happens when a pump fails?

Nothing you can feel. Pumps are N+1. The standby takes over, TP-View raises a warning, and the failed pump swaps out from the front.

IT and hardware ops

Can we pull a server without draining the rack?

Yes. Every tray sits on TP-Q12 dry-break couplings. Release, slide out, done. The rest of the rack keeps flowing.

What if something leaks?

The rope finds it to within 1 m. TP-LX closes that rack's valves and alerts your BMS. One rack goes quiet, the row keeps running.

Will it fit our server vendor's cold plates?

We map couplings and hose lengths to your server specs before the quote. If the vendor ships its own couplings, we match them.

Data center operations

What does the NOC see?

Every flow, pressure, temp and leak point, by rack, in your BMS and DCIM. Same names in TP-View and in your systems.

What maintenance does it need?

A coolant sample every quarter, which we test. Filter changes when TP-View says so. Both happen with the loop running.

Procurement

What is the warranty?

Five years on Arvane hardware, with advance replacement on pumps and controllers.

How is it priced?

Per rack kit, plus one CDU per row. Once Hall C is quoted, the next row is a known number.

What are the lead times?

Confirmed in writing with your quote, per kit, after the pilot closes.

13 · Next steps

From design review to a cool row.

Nine weeks from this review to a firm quote, with a pilot rack in the middle. Production timing is confirmed in writing with the quote.

1
Week 1Design review

Walk this kit with your mechanical, power and IT ops leads.

2
Week 2Site walk

Hall C, the facility water plant, and the busway.

3
Weeks 3-8Pilot rack

One rack at full load on a load bank. You test against the pass list.

4
Week 9Final design and quote

Heat loads, pipe sizes, power and lead times, in writing.

5
After POKits built and shipped

Pressure-tested, capped, labeled, one kit per rack.

6
CommissioningFill, flush, load test

Your integrator installs. We fill and prove it with your team.

For Corvia to decide

  • Facility water supply temp, and where row 1 taps in.
  • Headers overhead or under the floor.
  • Rack density target. 120 kW is drawn.
  • Rear doors on every rack, or only where needed.
  • N+1 inside one CDU, or two CDUs per row.
  • Coolant: PG25 or treated water.
  • BMS link: BACnet or Modbus. Pilot terms and pass list.

For Arvane to confirm before the quote

  • Heat load per rack from your server specs.
  • Pipe sizes and pressure drop, end to end.
  • CDU power against your busway.
  • Lead time for each kit, in writing.